DG 35380 B Trip Amp Currrents to 5A DC/AC 1 Transistor In -Rail-Bus
Current Monitoring Relay DG 35300
Monitoring of DC and AC current signals
The configurable Current Monitoring Relay DG 35300 is used for limit monitoring and processing of DC and AC current signals and mV signals for current measuring with shunt resistors. A SPST relay or optionally an isolated, passive transistor switch (Open-Collector) is available at the output.
Additional Information
General Data
| Switching error | DC: < 0.2 % full scale AC: < 0.5 % full scale | |
| Temperature coefficient | < 100 ppm/K | |
| Test voltage | 3 kV AC, 50 Hz, 1 Min., Input against output against power supply/In-Rail-Connector | |
| Working voltage 1) (Basic Insulation) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 | |
| Protection against electrical shock 1) | Protective Separation by reinforced insulation acc. to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply. | |
| Ambient temperature | Operation Transport and storage | 25 °C to +70 °C (-13 to +158 °F) 40 °C to +85 °C (-40 to +185 °F) |
| Power supply | 24 V DC, 16.8 V to 31.2 V DC, max. 1.0 W | |
| EMC 2) | EN 61326-1 | |
| Construction | 6.2 mm (0.244″) housing, protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 | |
| Connection | Captive plus-minus clamp screws Wire cross-section 0.5 to 2.5 mm2 / AWG 20-14 Stripped length 8 mm / 0.3 in Screw terminal torque 0.6 Nm / 5 lbf in | |
| Weight | Approx. 70 g | |

Need Any Help?
Thank you for your interest in Manotherm. If you have any questions about our products please call us on 01-452-2355